Underground Parking Lot Exhaust Fan
- Model No
-
TIV-200D, TIV-250D
- Features
-
Secure a good space due to non-installation of duct
Good installation and maintenance
Easy to make best ventilation by free installation structure
IP52 Motor
B insulation class
- Applications
-
Underground parking lots, shopping centers, factories, warehouses, etc
Drawings & Dimensions
(Unit:mm)
Performance Curve
Performance Data
Model | Impeller Size (mm) |
Source (V, Hz) |
Current (A) |
Pole (P) |
Input (W) |
Air Volume (㎥/h) |
Air Pressure | Rated Speed (RPM) |
Weight (Kg) |
|
---|---|---|---|---|---|---|---|---|---|---|
(mmAq) | (Pa) | |||||||||
TIV-200D | Ø205 | 220V ~, 60 | 0.90 | 2 | 185 | 1,800 | 3.0 | 29.4 | 3,120 | 17.5 |
220V ~, 50 | 0.76 | 150 | 1,560 | 2.3 | 22.5 | 2,710 | ||||
TIV-250D | Ø205 | 220V ~, 60 | 1.07 | 2 | 220 | 2,400 | 4.0 | 39.2 | 3,135 | 18.0 |
220V ~, 50 | 0.92 | 175 | 2,040 | 3.0 | 29.4 | 2,730 |